Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T13CM07159
Parcel: 117144860

Address:
356 W 18TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T13CM07159
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2014 MARTIN BROWN FIRE REVIEW Reqs Change A RESIDENCE BUILT UNDER THE INTERNATIONAL BUILDING CODE REQUIRES FIRE SPRINKLERS EITHER CHANGE COVER SHEET TO INDICATE INTERNATION RESIDENTIAL CODE OR ADD NOTE INDICATING FIRE SPRINKLERS WILL BE INSTALLED.
11/19/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 11-120-14
Activity: T14CM07159
Address: 356 W 18th St
Applicant: Scott Neeley

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Clarify references to sheet A-9 as indicated on sheets A-4 and S-1.
2. The City of Tucson has adopted the 2012 International family of codes. Correct references to the 2006 IRC on sheet P-1 or appeal must be made to the Building Official for alternate code use.

FLOOR PLAN:
3. Doors between a garage and a residence shall be self-closing, R302.5.1.

SECTIONS - DETAILS:
4. Provide continuous framing behind gypsum intersections or provide continuous gypsum from foundation to roof sheathing for fire rated wall assemblies, R302.1 as amended.

PLUMBING PLAN:
5. Cleanouts are required at the kitchen sink area, State amendment.


ELECTRICAL PLAN:
7. Specify minimum 6' separation of roof-top receptacles from the spa, E4203.1.1.
8. Indicate GFCI protection of receptacle at garage ceiling, E3902.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/24/2014 AROMERO4 OUT TO CUSTOMER Completed