Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM07148
Parcel: 140420740

Address:
7150 S TUCSON BL

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM07148
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/26/2013 STEVE SHIELDS ZONING REVIEW Passed
11/26/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide a mechanical design showing how the incinerator is to be installed in accordance with the IFGC and the manufacturer's instructions (e.g. venting, clearances, etc).
11/26/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/26/2013 ROBERT SHERRY WATER REVIEW Approved
11/26/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/26/2013 RSHERRY1 WWM REVIEW Passed No wastewater plumbing.
11/26/2013 KEN BROUILLETTE FIRE REVIEW Denied PLEASE INDICATE HOW THIS WILL COMPLY WITH NFPA 82 AND 603.8 OF THE 2012 IFC.

WHERE IS THE PRODUCT BEING STORED PRIOR TO GOING INTO THE INCINERATOR? IF INSIDE, NEED THE HEIGHT OF STORAGE, CLASSIFICATION OF STORAGE AND THE DENSITY OF THE FIRE SPRINKLER SYSTEM.
NEED THE SPECIFICATIONS OF THE INCINERATOR, NOT JUST THE MODEL NUMBER NOTED ON THE PLANS. NEED THE INSTALLATION INSTRUCTIONS AND VENTING/CHIMNEY SPECIFICATIONS. NEED TO KNOW THE HOURS OF OPERATION. PROVIDE
THE PLANS INDICATE THREE OCCUPANCY CLASSIFICATIONS, PLEASE INDICATE ON FLOOR PLAN THE LOCATION OF THESE OCCUPANCIES.
11/26/2013 JASON GREEN ENGINEERING REVIEW Approved
11/26/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/27/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Passed