Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/WWM
Permit Number - T13CM07120
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/20/2014 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T13CM07120 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. 1. A solar water system, or future installation preparation City of Tucson Ordinance #10549 is not required for an exterior water heater. 2. Gray water preparation, Ordinance #10579/11089 is not feasible for the existing drain system and a design not including a clothes washer. GENERAL COMMENTS: 1. Correct the "Foundation Only" permit number on sheet #1, 3 (2 places) and 4 to T11CM02619. 2. Inclusive Home Design Ordinance adopted by the City of Tucson Ordinance #10463 on 10/16/2007. Notate an accessible door with a maximum ½" threshold height, a 30" minimum net interior door width, lever-type door hardware, electrical outlet reachable range of 15" - 48" above floor, grab bar reinforcement of 2"x6" blocking at the toilet, tub and shower 36" above floor, and a second row at the tub 9" above the tub rim. 3. All SFR and Duplex plans submitted after July 1, 2009 require a solar photo-voltaic system, or future installation preparation City of Tucson Ordinance #10549 with the following provisions: 1. A 4 square feet area for (meter, disconnect & inverter) equipment adjacent to the electrical service panel or near the proposed collector panel space. 2. The best roof space available for accommodating PV solar collector panels with capacity for collector dead loading (typically 4 lbs/SF). 3. A minimum 3,800 volt-ampere PV electrical load entry on the Service Load Calculation (Show as a continuous load of 15.8 A). 4. An Electrical Panel Schedule with a 240 volt circuit breaker space labeled "reserved for Photo Voltaic". FLOOR PLANS: 1. Show a maximum ½" floor elevation change at a notated accessible route entrance on the floor plan, R106.1.1. 2. Provide all window sizes and types, and designate the operable portion of windows, as well as the location of tempered glass (24" of doorways), R308.4. PLUMBING PLANS: 1. Show hot water pipe with minimum R-3 insulation, N1103.4.2. ELECTRICAL PLANS: 1. The City of Tucson adopted the 2012 IRC with amendments on 1/1/2012. Show the current code reference at note #1. 2. Show compliance with the City of Tucson Ordinance #10549 for future Photo Voltaic on the panel schedule and electrical load calculation. 3. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm on each side of the bedroom doors in the immediate vicinity (hall). The kitchen is not an appropriate location. 4. Show receptacle outlets at wall spaces 2' or more with no wall point (exclude door openings) more than 6' from a receptacle outlet, E3901.2. Include the entry area of bedroom #2.. 5. Show receptacle outlets at each kitchen counter space wider than 12" with no point along the wall line more than 24" from a receptacle outlet, E3901.4.1. Show a countertop receptacle between the sink and range. 6. Protect all 15A & 20A proposed outlets (except bathrooms and kitchen) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12. 7. Provide notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, R4002.14. 8. Specify high-efficacy lamps for at least 75% of all lighting fixtures, N1104.1 OUTDOOR LIGHTING CODE 1. Show the proposed fixture as full cut-off FCO style, or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. Adjustable security light fixtures are unshielded, not FCO. INTERNATIONAL ENERGY CONSERVATION CODE: 1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, ceiling R=38 and walls R=13, N1102.1. Update the maximum "U" factor of the windows and doors at note #5 sheet #2. 2. Both standard and high density R-38 batt insulation requires a space greater than provided with 550S162 framing. Identify the product that provides the intended value, or provide an appropriate ceiling cavity space If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/22/2014 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
| 10/22/2014 | CPIERCE1 | REJECT SHELF | Completed |