Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM07048
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/20/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 11/20/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 11/21/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/21/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide load calculations for the two new A/C units. Reference: Section 101.4.3, IECC 2012. 2. Show that the proposed HVAC controls meet the requirements of Sections C403.2.4 and C403.3 (i.e. list the required contol features, not just a note requiring compliance with sections C403.2.4 and C403.3). Reference: Section C303.1, International Energy Conservation Code 2012. |
| 11/21/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET D1; KEY NOTES: NOTES D6.2 AND D6.4 WERE NOT LOCATED ON THE PLAN. VERIFY. 2. SHEET D1.1; KEY NOTES: NOTE D16.1 WAS NOT LOCATED ON THE PLAN. VERIFY. 3. SHEET A1 (FIRST FLOOR PLAN); KEY NOTES: TWO EXISTING COLUMNS AT THE LOBBY REFERENCE NOTE 5.3. REVISE THE REFERENCE NOTE TO 5.4. 4. SHEET A1; KEY NOTES: NOTES 6.4, 8.1, 9.1, 9.2, 15.2, 15.7, 16.1,16.2, AND 16.3 WERE NOT LOCATED ON THE PLAN. VERIFY. |
| 11/21/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/21/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 11/21/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/21/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/22/2013 | GERRY KOZIOL | WWM | REVIEW | Approved |