Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM07045
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/20/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 11/20/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/20/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/20/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/20/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET G002; CODE ANALYSIS: REMOVE THE TWO CITY OF CHANDLER REFERENCES AND THE ADAAG REFERENCE. 2. SHEET G003: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE NOTES. 3. SHEET G003: DARKEN THE TEXT. 4. SHEET A100; FLOOR PLAN: INDICATE THE HIGH/LOW DRINKING FOUNTAIN, OR THE SINGLE POINT OF USE WATER DISPENSER, ON THE PLAN. 5. SHEET A101: PROVIDE A DETAIL FOR THE NEW PARTITION WALL THAT EXTENDS TO THE EXISTING DECK. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 11/20/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 11/20/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/21/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/22/2013 | FRODRIG2 | WWM | REVIEW | Completed | |
| 11/22/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved |