Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM07037
Parcel: 10321342A

Address:
2112 W GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM07037
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
11/20/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation calculations using the Section 403.3, 2012 IMC.
2. The exhaust rate for the restroom shall be at least equal to the supply air flow rate.
3. Clarify the nature of the rooftop unit: heat pump or gas pack?
11/20/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a thermostatic mixing valve for the lavatory listed to ASSE 1070. The maximum hot water temperature shall be 110 degrees Fahrenheit.
2. Clarify the waste and vent piping diagram.
11/20/2013 ROBERT SHERRY WATER REVIEW Approved
11/20/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET D1.0; KEYNOTES: NOTES 6 AND 7 WERE NOT LOCATED ON THE PLAN. VERIFY.
2. SHEET A1.0; DETAIL AA: PROVIDE THE BRACE SIZE.
3. SHEET A1.0; INTERIOR PARTITION A; DETAIL 4: THE INTERIOR PARTITION A INDICATES THE WALL STOPS JUST ABOVE THE CEILING AND REQUIRES BRACING, WHILE DETAIL 4 INDICATES THE WALL EXTENDS TO THE EXISTING TRUSS AND REQUIRES NO ADDITIONAL BRACING. CLARIFY.
11/20/2013 JASON GREEN ENGINEERING REVIEW Approved
11/20/2013 MARTIN BROWN FIRE REVIEW Approved
11/20/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/27/2013 SPOWELL1 WWM REVIEW Needs Review
11/27/2013 SPOWELL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review