Permit Number: T13CM06956
Parcel: 125076370

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM06956
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
11/15/2013 LOREN MAKUS ENGINEERING REVIEW Approved
11/18/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide freeze protection for the supplies to the new sink.
2. The existing 2" gas pipe serving a load of 760 CFH appears to be undersized. Per Table 402.4(2), IFGC 2012, a minimum pipe size of 2-1/2" is required.
11/18/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/18/2013 KEN BROUILLETTE FIRE REVIEW Approved
11/18/2013 ROBERT SHERRY WATER REVIEW Approved
11/25/2013 FRODRIG2 ELECTRICAL-COMMERCIAL REVIEW Needs Review
11/25/2013 FRODRIG2 WWM REVIEW Needs Review
11/25/2013 FRODRIG2 BUILDING-COMMERCIAL REVIEW Needs Review
11/25/2013 FRODRIG2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review