Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM06956
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/15/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 11/15/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 11/18/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide freeze protection for the supplies to the new sink. 2. The existing 2" gas pipe serving a load of 760 CFH appears to be undersized. Per Table 402.4(2), IFGC 2012, a minimum pipe size of 2-1/2" is required. |
| 11/18/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/18/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 11/18/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/25/2013 | FRODRIG2 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/25/2013 | FRODRIG2 | WWM | REVIEW | Needs Review | |
| 11/25/2013 | FRODRIG2 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 11/25/2013 | FRODRIG2 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |