Permit Number: T13CM06879
Parcel: 13316003C

Address:
6675 E GRANT RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T13CM06879
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Chick Fil A @ Tanque Verde & Grant.
T13CM06879
Building Plan (Revision 1)

TRANSMITTAL DATE: November 18, 2015

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The site plan and civil sheets either need to be the revised approved sheets or remove the sheets from the building plan set.

3. Zoning will re-review the building plan on the next submittal.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
11/19/2015 MARTIN BROWN FIRE REVIEW Reqs Change Comments from previous submittal (revision 1) not addressed
12/03/2015 LOREN MAKUS ENGINEERING REVIEW Approved
12/04/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/07/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Comment not addressed. [Initial comment: If the carbon dioxide storage consists of more than two 50-pound cylinders, provide a mechanical exhaust system activated by an asphyxiant gas detection system. Reference: Tucson Fire Department Standard Operating Guideline for Compressed Gases dated 04/28/2015.]
12/07/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: The floor sink, P19A, located under the pot sink seems to have disappeared from the below slab plumbing plan but is still shown (albeit unlabeled) on the sanitary riser diagram. Reference: Section 107.2.1, IBC 2012.]
2. Comment not addressed. [Initial comment: The large CO2 storage tank appears to be blocking access to the prefabricated stop/backflow preventer panel, the beverage rack, and the remote lighting panel. Clarify how access will be provided to these items. Reference: Section 107.2.1, IBC 2012.]
3. Comment not addressed. [Initial comment: Clarify why an additional shut off valve and check valve on the cold water supply to the water heater have been installed between the hot water storage tank and the expansion tank. The new valves make the expansion tank unable to control thermal expansion in the storage tank. Reference: Section 607.3, IPC 2012.]
4. Comment not addressed. [Initial comment: The backflow preventer schedule on sheet P6.1 calls for a Watts LF7 dual check valve to be used for the coffee and tea brewers. Per Section 608.16.10, IPC 2012, an ASSE 1022 certified dual check valve with an atmospheric vent is required for used with coffee machines and non-carbonated beverage dispensers.]
5. Comment not addressed. [Initial comment: Include the additional area from the revised main entry tower in the roof drain calculations for the northeast roof drain. Reference: Section 1106, IPC 2012.]
12/14/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comment, also provide a written response.
#1. The commentary notes provided with the plan documents seem to be insufficient or lack the information necessary to clearly explain the extent of all the electrical changes in relation to all the Clouded in areas and Deltas referred to. For example, Delta #9 dated 6/24/15 ( owner Revision #7 ) References electrical plan sheets, E1.1,E1.2, E1.3, E2.1, E2.2, E2.2A, E2.3 etc. etc. The scope of changes as per the ( clouded in areas ) on all the plan sheets are numerous compared to the three items described as changes.
Please Clarify or Describe All the changes being made in detail to make it possible for a complete and accurate review. Ref: IBC sec. 107.2.1

Final Status

Task End Date Reviewer's Name Type of Review Description
12/15/2015 EGALLET1 APPROVAL SHELF Completed
12/15/2015 EGALLET1 OUT TO CUSTOMER Completed