Permit Number: T13CM06877
Parcel: 12902090A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM06877
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2013 MARTIN BROWN FIRE REVIEW Approved
11/13/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/13/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Passed
11/13/2013 ROBERT SHERRY WATER REVIEW Approved
11/13/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A.2; ROOF PLAN: KEYNOTES 6, 9, AND 10 WERE NOT LOCATED ON THE PLAN. VERIFY.
2. SHEET A.2; ROOF PLAN: KEYNOTE 17 LOCATED IN THE SOUTHWEST CORNER OF THE PLAN IS NOT IN THE KEYNOTES. PROVIDE.
3. SHEET A.3; ELEVATIONS: KEYNOTE 11 WAS NOT LOCATED ON THE ELEVATIONS. VERIFY.
4. SHEET S.2 (FRAMING PLAN); STRUCTURAL CALCULATIONS (SHEET 4): BEAM B-2 IN THE CALCULATIONS AT THE NORTHWEST CORNER OF THE PLAN IS SHOWN AS A 5 1/8" X 12" GLB, WHILE SHEET S.2 INDICATES KEYNOTE 1 (STEEL TUBE BEAM). CLARIFY.
5. SHEET S.2; STEEL FRAMING LAYOUT: INDICATE THE TYPICAL TUBE SIZE ON THIS PLAN.
6. SHEET S.3 (DETAIL 1); STRUCTURAL CALCULATIONS (SHEET 9): THE CALCULATIONS INDICATE A BRACE SIZE OF A 4X4X1/4 ANGLE, WHILE THE DRAWING INDICATES A 3 1/2 X 3 1/2 X 1/4 ANGLE. CLARIFY.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/13/2013 RSHERRY1 WWM REVIEW Passed No wastewater plumbing.
11/13/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide roof drainage calculations and plans; include the effect of any vertical walls that can divert rainfall onto the roof. Show how overflow protection is provided for the roof. Reference: Sections 1101, 1106 and 1108, IPC 2012.
11/13/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/15/2013 SPOWELL1 ENGINEERING REVIEW Needs Review
11/15/2013 SPOWELL1 ZONING REVIEW Needs Review