Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T13CM06855
Parcel: 13709007D

Address:
5408 S 12TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM06855
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/12/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. UP TO 20% OF THE PROJECT COST MUST BE USED TO IMPROVE ACCESSIBILITY ISSUES. GRAB BARS IN THE RESTROOMS MIGHT BE A GOOD APPLICATION OF THIS. PROVIDE A DETAIL ON THE DRAWING, INDICATING WHAT ISSUES WILL BE ADDRESSED FOR THIS. IF IT IS RESTROOM GRAB BARS, SHOW THE DETAIL FROM FIGURE 604.5.1 FROM THE 2009 ICC/ANSI.
11/12/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied 1. Need a one line diagram ofm service
2. Show upgraded feeders to upgraded panel
3.New panel shows 42 k aic, why if your fault current at new panel is only 6,000 plus ?
4. What about lighting and power in incorporated area ?

RT Majuta
11/12/2013
11/12/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/20/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation calculations for the new areas.
2. Provide a 4" diameter exhaust duct for the dryer.
11/20/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the waste piping design.
2. Provide water hammer arrestors for the clothes washer.
11/20/2013 ROBERT SHERRY WATER REVIEW Approved
11/20/2013 SPOWELL1 ZONING REVIEW Needs Review
11/20/2013 SPOWELL1 WWM REVIEW Needs Review
11/20/2013 SPOWELL1 FIRE REVIEW Needs Review
11/20/2013 SPOWELL1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/20/2013 SHANAE POWELL OUT TO CUSTOMER Completed