Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM06855
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/12/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. UP TO 20% OF THE PROJECT COST MUST BE USED TO IMPROVE ACCESSIBILITY ISSUES. GRAB BARS IN THE RESTROOMS MIGHT BE A GOOD APPLICATION OF THIS. PROVIDE A DETAIL ON THE DRAWING, INDICATING WHAT ISSUES WILL BE ADDRESSED FOR THIS. IF IT IS RESTROOM GRAB BARS, SHOW THE DETAIL FROM FIGURE 604.5.1 FROM THE 2009 ICC/ANSI. |
11/12/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Need a one line diagram ofm service 2. Show upgraded feeders to upgraded panel 3.New panel shows 42 k aic, why if your fault current at new panel is only 6,000 plus ? 4. What about lighting and power in incorporated area ? RT Majuta 11/12/2013 |
11/12/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
11/20/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide ventilation calculations for the new areas. 2. Provide a 4" diameter exhaust duct for the dryer. |
11/20/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the waste piping design. 2. Provide water hammer arrestors for the clothes washer. |
11/20/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/20/2013 | SPOWELL1 | ZONING | REVIEW | Needs Review | |
11/20/2013 | SPOWELL1 | WWM | REVIEW | Needs Review | |
11/20/2013 | SPOWELL1 | FIRE | REVIEW | Needs Review | |
11/20/2013 | SPOWELL1 | ENGINEERING | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/20/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |