Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2013 MARTIN BROWN FIRE REVIEW Approved
11/26/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET G1.1; APPLICABLE CODES: REVISE THE ICC/ANSI EDITION TO THE 2009.
2. SHEET G2.2; PROJECT DATA (OCCUPANCY SEPARATIONS): REVISE THE REFERENCED IBC SECTION AND TABLE.
3. SHEET G2.2; PROJECT DATA (MINIMUM INTERIOR FINISH FLAME SPREAD): REVISE THE REFERENCED IBC TABLE.
4. SHEET G2.2; PROJECT DATA (MINIMUM CORRIDOR EGRESS WIDTH): REVISE THE REFERENCED IBC SECTION.
5. SHEET G2.2; PROJECT DATA (MINIMUM CORRIDOR WIDTH FOR BED): REVISE THE REFERENCED IBC SECTION.
6. SHEET G2.2; PROJECT DATA (MINIMUM CLEAR EGRESS DOOR WIDTH): REVISE THE REFERENCED IBC SECTION.
7. SHEET G2.2; PROJECT DATA (MINIMUM NUMBER OF EXITS REQUIRED): REVISE THE REFERENCED IBC SECTION.
8. SHEET A5.1; KEYNOTES: NOTE 15 WAS NOT LOCATED ON THE ELEVATIONS. VERIFY.
9. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/27/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/29/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/11/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/12/2013 ROBERT SHERRY WATER REVIEW Approved
12/12/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/13/2013 CPIERCE1 REJECT SHELF Completed