Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM06849
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/20/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/26/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET G1.1; APPLICABLE CODES: REVISE THE ICC/ANSI EDITION TO THE 2009. 2. SHEET G2.2; PROJECT DATA (OCCUPANCY SEPARATIONS): REVISE THE REFERENCED IBC SECTION AND TABLE. 3. SHEET G2.2; PROJECT DATA (MINIMUM INTERIOR FINISH FLAME SPREAD): REVISE THE REFERENCED IBC TABLE. 4. SHEET G2.2; PROJECT DATA (MINIMUM CORRIDOR EGRESS WIDTH): REVISE THE REFERENCED IBC SECTION. 5. SHEET G2.2; PROJECT DATA (MINIMUM CORRIDOR WIDTH FOR BED): REVISE THE REFERENCED IBC SECTION. 6. SHEET G2.2; PROJECT DATA (MINIMUM CLEAR EGRESS DOOR WIDTH): REVISE THE REFERENCED IBC SECTION. 7. SHEET G2.2; PROJECT DATA (MINIMUM NUMBER OF EXITS REQUIRED): REVISE THE REFERENCED IBC SECTION. 8. SHEET A5.1; KEYNOTES: NOTE 15 WAS NOT LOCATED ON THE ELEVATIONS. VERIFY. 9. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 11/27/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/29/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/11/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/12/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/12/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/13/2013 | CPIERCE1 | REJECT SHELF | Completed |