Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM06822
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/08/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 11/08/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/08/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/08/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/08/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/08/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 11/08/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 11/08/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 11/08/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/14/2013 | CPIERCE1 | WWM | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/10/2015 | CPIERCE1 | APPROVAL SHELF | Completed |
| 03/10/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |