Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T13CM06821
Parcel: 13219112A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM06821
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2013 STEVE SHIELDS ZONING REVIEW Approved
11/08/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/08/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13cm06821

1. Sheet E103, circuit T 32,34,36 for disconnect RTU-3 shown in panel for circuit to Panel G.
2. Sheet E103, circuits G 41,43,45 for refrigeration unit has 45 marked for spare in panel.
3.Sheet E103, circuit G1 is shown for lighting, panel G has circuit 1 as part of 3 phase circuit for freezer ?

Please review circuitry for correct locations.

Ray T Majuta
Elect Plan Review
PDSD, Tucson
11/8/2013
11/08/2013 ROBERT SHERRY WATER REVIEW Approved
11/08/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/08/2013 JASON GREEN ENGINEERING REVIEW Approved
11/08/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Correct the waste and vent riser diagram on sheet P103 to provide indirect waste pipes for each compartment of the 3-compartment sink (i.e. no direct waste connectons). Reference: Section 802.1.8, IPC 2012.
11/08/2013 KEN BROUILLETTE FIRE REVIEW Approved
11/08/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/03/2013 SPOWELL1 WWM REVIEW Needs Review