Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM06821
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/08/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
11/08/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
11/08/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13cm06821 1. Sheet E103, circuit T 32,34,36 for disconnect RTU-3 shown in panel for circuit to Panel G. 2. Sheet E103, circuits G 41,43,45 for refrigeration unit has 45 marked for spare in panel. 3.Sheet E103, circuit G1 is shown for lighting, panel G has circuit 1 as part of 3 phase circuit for freezer ? Please review circuitry for correct locations. Ray T Majuta Elect Plan Review PDSD, Tucson 11/8/2013 |
11/08/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/08/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/08/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
11/08/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Correct the waste and vent riser diagram on sheet P103 to provide indirect waste pipes for each compartment of the 3-compartment sink (i.e. no direct waste connectons). Reference: Section 802.1.8, IPC 2012. |
11/08/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
11/08/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
12/03/2013 | SPOWELL1 | WWM | REVIEW | Needs Review |