Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM06820
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/08/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 11/08/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/08/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T13CM06820 Same items denied as for T13cm06821. Ray T Majuta PDSD, Tucson Elect Plan Review 11/8/2013 |
| 11/08/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/08/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/08/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 11/08/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Correct the waste and vent riser diagram on sheet P103 to provide indirect waste pipes for each compartment of the 3-compartment sink (i.e. no direct waste connectons). Reference: Section 802.1.8, IPC 2012. |
| 11/08/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 11/08/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/03/2013 | SPOWELL1 | WWM | REVIEW | Needs Review |