Review Date Reviewer's Name Type of Review Description Status Comments
11/27/2013 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T13CM06803
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide revised plans and calculations, highlighting any changes or with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2012 IRC with amendments on 1/1/2012. Show the current code reference on the plans.

PLUMBING PLANS:

1. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Show section A & B with 1-1/4" pipe; C with 1" pipe; E with ¾" pipe and F with ¾" pipe.

ELECTRICAL PLANS:

1. Use Table E3705.1 for sizing 30 AMP branch circuit conductors and protection ratings with 75 degree copper conductor. Change the oven circuit #B-25/27 conductor to #8.
2. The kitchen countertop receptacle outlet circuit may not serve other locations, E3703.2 and E4001.3.1 through E4001.4.5. Change circuit # B-14 on the plan.
3. Protect all 15A & 20A proposed outlets (except bathrooms and kitchen) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12 & 13. Update note #H with "new or extended" replacing "bedroom".