Permit Number: T13CM06781
Parcel: 124091480

Address:
1816 E 10TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T13CM06781
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2013 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T13CM06781
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide revised plans and calculations, highlighting any changes or with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

1. Provide sheet #9.

SECTIONS - DETAILS:

1. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c ceiling framing, IRC table R702.3.5 footnote d.
2. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2. Update note #4, sheet 3 and on the mechanical plan.
3. Specify water-resistive barrier equivalent to two layers of Grade D paper over the wood based sheathing of exterior plaster wall coverings, R703.6.3.

PLUMBING PLANS:

1. Show hot water pipe with minimum R-3 insulation, N1103.4.2.
2. Show a pressure and temperature relief valve at the water heater. Note a metallic T&P line terminating at the exterior 6 inches above grade facing down, P2803.6.1.
3. Provide a water hammer arrester for quick-closing valves serving the clothes washer, P2903.5.
4. Show plumbing vents (VTR) within acceptable distances from traps, P3105.1. (1 ½"-6', 2"-8', 3"-12').
5. Show a clean out at the kitchen sink area, State amendment.

MECHANICAL PLANS:

1. Show a sheet number.
2. Show supply ducts with minimum R-8 insulation (includes vented attics) except when completely located inside the thermal envelope, N1103.2.1. All other ducts require R-6 insulation.
3. Provide return air duct and register sizes meeting minimum requirements of 72 SQ IN/ ton, M1403. Minimum duct/register size: heat pump or air conditioner - 6 SQ IN per 1,000 BTU (1 ton cooling = 12,000 BTU). The 5 ton unit requires a minimum 22" diameter return air duct.
4. Show dryer vent size and location for venting to exterior, M1501.
5. Show bathroom exhaust fan locations with minimum 50 CFM rating and duct to the exterior, R303.3 and M1507.3.

ELECTRICAL PLANS:

1. Show a main breaker that disconnects all service when the panel has more than six switches or breakers, E3601.7.
2. Show receptacle outlets at each kitchen counter space with no point along the wall line more than 24" from a receptacle outlet, E3901.4.1. Add a receptacle outlet (circuit #11 or 12) over the dishwasher; circuit #23 serves the dishwasher below the countertop.
3. Hallways of 10' or more in length require a receptacle, E3901.10.
4. Provide notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, R4002.14.
5. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, N1102.1. Show the correct "U" factor for windows at note #3, sheet 3 and note #3 on the mechanical plan.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/12/2013 CPIERCE1 REJECT SHELF Completed