Permit Number: T13CM06769
Parcel: 126192020

Address:
4303 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM06769
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approv-Cond Conditional Approval is provided upon a later submittal, no later than 1 week from today, of calaculaions and drawing revisions for the comments stated:
1. Show structural suspension detail for both exhaust hoods and supporting structural calculations.
2. Provide an architectural detail of the wall behind the exhaust hood showing non combustable and finish materials required by code.
3. Show structural calculations details for joist modifications on the drawings.
END OF REVIEW
12/03/2013 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Approved