Permit Number: T13CM06759
Parcel: 116193740

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM06759
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/21/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Calculate the total outside air flow for each air handler based on Section 403.3.2.3, IMC 2012, "Multiple zone recirculating systems". The occupant diversity is equal to 1.0, not 0.6; the architect has stated that the maximum number of expected occupants will be greater than the occupancy based on Table 403.3, IMC 2012. Check the arithmetic. [Third comment: This activity has two separate air handlers, each serving multiple zones. Calculate the total outside air flow for each air handler based on Section 403.3.2.3, IMC 2012, "Multiple zone recirculating systems".] [Second comment: Revise the number of occupants in each space, using the occupant density shown in Table 403.3, IPC 2012. Revise the occupancy type for rooms 101 and 120, using "office: main entry lobby" for room 101 and "office: reception" for room 120. Calculate the total outside air flow for each air handler based on Section 403.3.2.3, IMC 2012, "Multiple zone recirculating systems".] [Initial comment: Clarify the occupancy classifications and the occupant density used in the ventilation calculations. The occupancy classifications should closely match the actual occupancy and the occupant density used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2012 or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3, IMC 2012.]

Final Status

Task End Date Reviewer's Name Type of Review Description
01/23/2014 CPIERCE1 REJECT SHELF Completed