Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM06759
Parcel: 116193740

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM06759
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2014 ROBERT SHERRY WATER REVIEW Approved
01/09/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Water heater detail 1/P0.01 contradicts water heater detail 5/P0.02. [Second comment: No design for the mounting shelf or any structural calculations appear to have been included with the current submittal. The design for the mounting shelf must be included with the drawing set.] [Initial comment: Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported from the building structure. Reference: Section 301.2, IPC 2012.]
2. Comment not addressed on plumbing sheets P0.01 and P3.01. [Initial comment: Note: Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that in addition to signing the seal, the registrant shall include the date the document was sealed and that a notation shall be placed beneath the seal, written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).]
01/09/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. This activity has two separate air handlers, each serving multiple zones. Calculate the total outside air flow for each air handler based on Section 403.3.2.3, IMC 2012, "Multiple zone recirculating systems". [Second comment: Revise the number of occupants in each space, using the occupant density shown in Table 403.3, IPC 2012. Revise the occupancy type for rooms 101 and 120, using "office: main entry lobby" for room 101 and "office: reception" for room 120. Calculate the total outside air flow for each air handler based on Section 403.3.2.3, IMC 2012, "Multiple zone recirculating systems".] [Initial comment: Clarify the occupancy classifications and the occupant density used in the ventilation calculations. The occupancy classifications should closely match the actual occupancy and the occupant density used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2012 or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3, IMC 2012.]
2. Comment not addressed on mechanical sheets M0.01, M0.03, M0.04, M0.05, M2.01, M2.02, M4.01, M4.02, and M4.ROOF. [Initial comment: Note: Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that in addition to signing the seal, the registrant shall include the date the document was sealed and that a notation shall be placed beneath the seal, written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).]

Final Status

Task End Date Reviewer's Name Type of Review Description
01/17/2014 CPIERCE1 REJECT SHELF Completed