Permit Number: T13CM06736
Parcel: 10309006D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM06736
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2013 STEVE SHIELDS ZONING REVIEW Approved
11/05/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide heating and cooling load calculations to justify the size of the new heat pump.
2. Revise the capacity of the exhaust fan for the men's restroom - 50 CFM per water closet or urinal.
3. Verify that the total airflow for HP-2 complies with the manufacturer's listing instructions. Coordinate the airflow with the mechanical plan.
4. Correct the area of the computer room in the ventilation calculations. Coordinate the balancing data for HP-2 in the ventilation calculations and in the equipment schedule.
11/05/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/05/2013 ROBERT SHERRY WATER REVIEW Approved
11/05/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/05/2013 LOREN MAKUS ENGINEERING REVIEW Approved
11/05/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide tempering valves listed to comply with ASSE 1070 for the lavatories.Limit the hot water temperature to 110 degrees Fahrenheit.
2. Install the vacuum relief valve for the water heater per the manufacturer's instructions (i.e. no valves between the relief valve and the water heater).
11/05/2013 KEN BROUILLETTE FIRE REVIEW Approved
11/05/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/08/2013 FRODRIG2 WWM REVIEW Completed