Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T13CM06704
Parcel: 12108001B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM06704
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
11/04/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the ventilation calculations using the 2012 IMC , not the 2006 IMC.
2. Revise the energy compliance notes to the 2012 IECC.
11/04/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/04/2013 ROBERT SHERRY WATER REVIEW Denied Provide the size of the water meter, the size of the reduced pressure backflow preventer, and the total demand on the meter.
11/04/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/04/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a vacuum relief valve for the water heatewr. reference: Section 504.2, IPC 2012.
2. Provide a pan drain for the water heater. Reference: Section 504.7, IPC 2012.
3. Revise the water heater detail to show the water heater piping in compliance with the manufacturer's listing instructions. Reference: Sections 502.1 and 607.2, IPC 2012.
4. Clarify how the water heater is to be supported.
11/04/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/07/2013 SPOWELL1 WWM REVIEW Needs Review
11/07/2013 KEN BROUILLETTE FIRE REVIEW Approved
11/07/2013 JASON GREEN ENGINEERING REVIEW Approved