Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM06704
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/04/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
11/04/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the ventilation calculations using the 2012 IMC , not the 2006 IMC. 2. Revise the energy compliance notes to the 2012 IECC. |
11/04/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/04/2013 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide the size of the water meter, the size of the reduced pressure backflow preventer, and the total demand on the meter. |
11/04/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/04/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a vacuum relief valve for the water heatewr. reference: Section 504.2, IPC 2012. 2. Provide a pan drain for the water heater. Reference: Section 504.7, IPC 2012. 3. Revise the water heater detail to show the water heater piping in compliance with the manufacturer's listing instructions. Reference: Sections 502.1 and 607.2, IPC 2012. 4. Clarify how the water heater is to be supported. |
11/04/2013 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
11/07/2013 | SPOWELL1 | WWM | REVIEW | Needs Review | |
11/07/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
11/07/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved |