Permit Number: T13CM06628
Parcel: 12513002E

Review Status: Completed

Review Details: OTHER

Permit Number - T13CM06628
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The new drawing shows that office 111 and accessory rehersal 105 both utilize an egress corridor for air return. Revise the air movement as required to avoid using the egress corridor as a duct. Rference: Section601.2, IMC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/14/2013 AROMERO4 OUT TO CUSTOMER Completed