Review Details: COMMERCIAL - TI

Permit Number - T13CM06589
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide structural calculations from a structural engineer for all structural changes required to support the new exhaust hood.
2. Please provide structural calculations from a structural engineer for the support of the exhaust hood including connection details of all suppoprt rods to the existing structure.
3. Manufactures installation brochures are not structural calculations.
END OF REVIEW
11/29/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/02/2013 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Needs Review
12/02/2013 CPIERCE1 MECHANICAL-COMMERCIAL REVIEW Needs Review