Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/22/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Please provide structural calculations from a structural engineer for all structural changes required to support the new exhaust hood. 2. Please provide structural calculations from a structural engineer for the support of the exhaust hood including connection details of all suppoprt rods to the existing structure. 3. Manufactures installation brochures are not structural calculations. END OF REVIEW |
11/29/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/02/2013 | CPIERCE1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
12/02/2013 | CPIERCE1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review |