11/15/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM06589
2017 E Irvington, 117

1. Item 2 requested lasr review, provide load on Service not
submitted.
2. Fault current for 1200 amp 120/208 volts 3 phase service is not 48,300 aic on plan , Tucson Electric list 75,100 aic in Service Requirement Book 2012.

Ray Majuta
Elect Plan Review
PDSD, Tucson
11/15/2013