Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM06589
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/15/2013 | FRODRIG2 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
11/15/2013 | ERICA SANCHEZ | WWM | REVIEW | Approved | |
11/15/2013 | FRODRIG2 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
11/15/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/15/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM06589 2017 E Irvington, 117 1. Item 2 requested lasr review, provide load on Service not submitted. 2. Fault current for 1200 amp 120/208 volts 3 phase service is not 48,300 aic on plan , Tucson Electric list 75,100 aic in Service Requirement Book 2012. Ray Majuta Elect Plan Review PDSD, Tucson 11/15/2013 Ray.Majuta@tucsonaz.gov 520-837-4988 |
11/15/2013 | FRODRIG2 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review |