10/29/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
10/29/2013 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
10/29/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM06589 2017 E Irvington #117 1. Provide size of service in ampacity. 2. Provide total load on service including this space. 3. Provide fault current at service , main disconnect and panel A. 4. Panel A listed at 22,000 aic, are circuit breakers to be listed 22,000 aic also ? 5. Could not find circuits 37,38,40,42,44,46 on plan. Ray Majuta PDSD, Tucson Elect Plan Review 520-837/4988 Ray.Majuta@tucsonaz.gov |
10/29/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Provide structural calculations and details for the pizza oven exhaust hood. |
10/29/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
10/29/2013 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
11/15/2013 | SPOWELL1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
11/15/2013 | SPOWELL1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
11/15/2013 | SPOWELL1 | WATER | REVIEW | Needs Review | |
11/15/2013 | SPOWELL1 | WWM | REVIEW | Needs Review |