Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T13CM06589
Parcel: 132191220

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM06589
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2013 STEVE SHIELDS ZONING REVIEW Approved
10/29/2013 LAITH ALSHAMI ENGINEERING REVIEW Approved
10/29/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM06589
2017 E Irvington #117

1. Provide size of service in ampacity.
2. Provide total load on service including this space.
3. Provide fault current at service , main disconnect and panel A.
4. Panel A listed at 22,000 aic, are circuit breakers to be listed 22,000 aic also ?
5. Could not find circuits 37,38,40,42,44,46 on plan.


Ray Majuta
PDSD, Tucson
Elect Plan Review
520-837/4988
Ray.Majuta@tucsonaz.gov
10/29/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied Provide structural calculations and details for the pizza oven exhaust hood.
10/29/2013 MARTIN BROWN FIRE REVIEW Approved
10/29/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/15/2013 SPOWELL1 MECHANICAL-COMMERCIAL REVIEW Needs Review
11/15/2013 SPOWELL1 PLUMBING-COMMERCIAL REVIEW Needs Review
11/15/2013 SPOWELL1 WATER REVIEW Needs Review
11/15/2013 SPOWELL1 WWM REVIEW Needs Review