Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T13CM06530
Parcel: 14028019A

Address:
6220 S TUCSON BL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM06530
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2013 STEVE SHIELDS ZONING REVIEW Approved
11/25/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/29/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. Provide information on the drawings to coordinate with the component descriptions used in COMcheck (e.g. show the continuous insulation used for the roof and for the floor located over an unconditioned space). Complete the Envelope Compliance Certificate by checking the appropriate line items in Section 3, the Air Leakage, Component Certification, and Vapor Retarder Requirements. [Initial comment: The operations office is heated and cooled with a heat pump; verify that the operations office has been included in the envelope energy calculations. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information on the drawing shall, as a minimum, include the R-values of the insulation. Complete the Envelope Compliance Certificate by checking the appropriate line items in Section 3, the Air Leakage, Component Certification, and Vapor Retarder Requirements. Supporting documentation shall be either on the drawings or in the project manual. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012.]
11/29/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The proposed temperature mixing valve (Symmons model 7-400A) is listed as being CSA B125.3 compliant but not ASSE 1070 which is specifically required by Section 607.1.1, IPC 2012. [Initial comment: Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Sections 416.5 and 607.1, IPC 2012 and Section C404.3, IECC 2012.]
12/02/2013 LAITH ALSHAMI ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/04/2013 CPIERCE1 REJECT SHELF Completed