Permit Number: T13CM06488
Parcel: 11303097B

Address:
3701 N PARK AV

Review Status: Completed

Review Details: WALK THRU - RES

Permit Number - T13CM06488
Review Name: WALK THRU - RES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2013 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 10-24-13
Activity: T13CM06488
Address: 3701 N Park Av
Applicant: Silverado Plumbing

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Specify size of electrical service, E3602.2. Note: Electrical services less than 150 amps must include an electrical load calculation to justify system capacity.
2. Specify roof framing and/or equipment supports capable of accommodating the proposed equipment load.
3. Provide Manual J/S/D calculations for the forced air unit in accordance with M1401.3, M1601.1.
4. The attached template has been provided for your convenience and can be found online at
http://cms3.tucsonaz.gov/files/dsd/Permit-review/Air_Conditioning_Template.pdf


If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review