Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM06451
Parcel: 129060680

Address:
2614 E 19TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T13CM06451
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2013 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 11-18-13
Activity: T13CM06451
Address: 2614 E 19th St
Applicant: Jesus Robles

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

STRUCTURAL / FRAMING PLAN:
1. Projections shall not extend to a point closer than 2 feet from the line used to determine the fire separation distance. Projections extending into the fire separation distance shall have not less than one-hour fire-resistive construction on the underside, 2012 Amendment R302.1.

PLUMBING PLAN:
2. Specify a minimum 1" water supply line from the water meter for the proposed fixture demand.
3. Correct mislabeled code reference on water supply fixture unit calculation and provide water supply values consistent with the designed length of water supply piping.
4. Clarify clean out location outside building. Dead end branches are not permissible and clean outs must allow cleaning in the direction of flow, P3005.
5. Provide vent size for utility sink, P3101.1.

ELECTRICAL PLAN:
6. The GFCI protected receptacle in the bathroom may not share the circuit with receptacles located in the utility and storage rooms, E3703.4, E3901.6.
7. Specify faceplate grounding per E4001.11.1.
8. Specify tamper resistant receptacles per E4002.14.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/20/2013 AROMERO4 OUT TO CUSTOMER Completed
11/20/2013 CPIERCE1 REJECT SHELF Completed