Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/WWM
Permit Number - T13CM06413
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/14/2013 | CLAYTON TREVILLYAN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | PLAN REVIEW COMMENTS Date: 11-18-13 Activity: T13CM06413 Address: 2218 E Louisiana St Applicant: Brenda Zepeda This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval. FLOOR PLAN: 1. Specify the minimum space required in front of showers: not less than 30" wide and 24", Figure R307.1. 2. Specify cement, fiber-cement, or glass-mat board backing in tub/shower enclosures, R307.2, R702.4.2. Moisture resistant gypsum board is not an approved surface for tiled areas. PLUMBING PLAN: 3. The water meter assigned to this property (#04010744) is a 5/8" meter. Correct plan notation for existing meter size. 4. Show the cleanout at the junction of building drain and building sewer. Two-way cleanout within 2' from the building, P3005.2. MECHANICAL PLAN: 5. Provide Manual J/S/D calculations for the forced air unit in accordance with M1401.3, M1601.1. 6. Show dryer vent size and location for venting to exterior (max 25' w/bend reductions), M1502. 7. Provide location of return air ducts and register sizes, M1602. Minimum duct/register size: heat pump or air conditioner - 6 sq. in. / 1000 BTU, M1403.1 (1 ton cooling = 12,000 BTU). ELECTRICAL PLAN: 8. All meters shall be located on an exterior house or garage wall, but not under a carport, breezeway, patio, porch, or area that can be enclosed with building expansion, TEP SR-405. OUTDOOR LIGHTING CODE 9. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Model plans should specify a minimum lot size for the proposed exterior lighting. INTERNATIONAL ENERGY CONSERVATION CODE: 10. Specify the "R" value of the insulation, as well as the "U" factor and the solar heat gain coefficient of the windows and doors. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.40, SHGC=0.25, ceiling R=38. Mass wall requirement is R=4 when 50% of insulation is exterior and R=6 when applied interior, N1102.1. If you have any questions please contact: Clayton Trevillyan 520.837.4913 Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/14/2014 | CPIERCE1 | REJECT SHELF | Completed |