Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T13CM06405
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/13/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The envelope components shown on the drawing do not correspond to the components used in the calculations (e.g. the roof insulation in COMcheck is a "sag & bag" installation but the drawings show the roof insulation on the hard lid of the room, etc.). [Initial comment: Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.] 2. What conditions lead to the exhaust fan, EF-2, being switched on? [Initial comment: Provide the sequence of operation for EF-2. Reference: Section 107.2.1, IBC 2012.] |
| 12/13/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the note at the bottom of the plumbing schedule to agree with the revised demand calculation. [Initial comment: The fixture unit method of calculating the instantaneous water demand for a plumbing system uses the probability of group of plumbing fixtures operating with differing flow rates and different use frequencies. Provide justification for including the continuous supply demand for the car wash equipment as part of the plumbing fixture unit calculation. Reference: Section 604.1 and E102.2.2, IPC 2012.] 2. Clarify the location of RPBP-1, its size, and the size of the pipe entering and leaving RPBP-1. Show how the RP is readily accessible if it is located in the ceiling space. (Also, correct detail 207 to show water piping, not compressed air piping.) [Initial comment: Show how contamination of the water distribution system due to connections to process equipment is prevented. (Also, correct detail 207 to show water piping, not compressed air piping.) Reference: Section 608.1, IPC 2012.] 3. The plumbing schedule still shows a 1-1/2" supply to the water closet. [Initial comment: Clarify the type of water closet being installed. The Plumbing Schedule on sheet P-1 shows a flush valve water closet with a 1-1/2" water supply but with the fixture units of a tank-type water closet. Sheet P-2 (which shows a ¾" supply serving the water closet, lavatory, and a hose bibb) and the plumbing specifications on sheet P-4 which calls for a flush-tank water closet. Reference: Section 107.2.1, IBC 2012.] |
| 12/20/2013 | SPOWELL1 | ZONING | REVIEW | Needs Review | |
| 12/20/2013 | SPOWELL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/20/2013 | SPOWELL1 | ENGINEERING | REVIEW | Needs Review | |
| 12/20/2013 | SPOWELL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |