Permit Number: T13CM06395
Parcel: 13416205D

Address:
7201 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM06395
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2013 KEN BROUILLETTE FIRE REVIEW Approved
10/24/2013 JEFF DRUMM LANDFILL REVIEW Approved
10/28/2013 MICHAEL ST. PAUL ZONING REVIEW Reqs Change Approval of DP13-0148 required.
10/28/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
10/28/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
10/30/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/15/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Demonstrate energy code compliance for the building envelope using calculations based on the current code. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C101.3, C101.5, C103.2, and C401.2, IECC 2012.
2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
3. Verify that the HVAC unit controls have been provided with an automatic start capability. Reference: Section C403.2.4.3.3, IECC 2012.
4. Clarify how excess outside air relief from the building is to be accomplished. Reference: Section C403.3.1.1.4, IECC 2012.
11/15/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the waste and vent riser diagram to coordinate with the plumbing plan. Reference: Section 107.2.1, IBC 2012.
2. The developed length of the hot water supply piping appears to be greater than fifty feet and detail 7/P.0 indicates the presence of a recirculating hot water system; show the return hot water piping on the plumbing plan and the water riser diagram. Reference: Section 607.2, IPC 2012.
3. Show the required flow rate for the hot water recirculating pump.
11/15/2013 ROBERT SHERRY WATER REVIEW Approved
11/18/2013 LOREN MAKUS ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/18/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed