Permit Number: T13CM06388
Parcel: 117150050

Address:
98 E CONGRESS ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T13CM06388
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2013 DAVID RIVERA ZONING REVIEW Approved
11/15/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/15/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Non responsive to original plan review comments. Please provide revisions to all comments and resubmit.
a. Specifically comments 2, 3, 5a, 6, 9, and 10.
2. Please define your mezzanine as per the requirements of the 2012 IBC, Section 505. If you still feel it is a mezzanine please provide exact code analysis as to why.
3. Adjust the overall width of the accessible toilet room to accommodate the 5'-0" water clearance requirement.
4. No Plumbing drawings.
5. Please respond in writing to all review comments.
END OF REVIEW
11/15/2013 LOREN MAKUS ENGINEERING REVIEW Approved
11/27/2013 FRODRIG2 PLUMBING-COMMERCIAL REVIEW Needs Review
11/27/2013 FRODRIG2 FIRE REVIEW Needs Review
11/27/2013 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
11/27/2013 FRODRIG2 MECHANICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/27/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed