Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM06379
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/29/2013 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: LoanMax Title Loans - 1306 West Grant T13CM06379 Building Plan (1st Review) TRANSMITTAL DATE: October 29, 2013 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Remove the development package from the building plans as they are two separate submittals that can run concurrently. 3. The development package does not match the architectural site plan and building plan. There is an expansion proposed at the southwest corner of the building and bollards called out in different places on the architectural plans. The building plans should match the development package. 4. Until the development package has been approved the building plans cannot be approved. 5. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
11/01/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/05/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show that each heat pump thermostatic control provides for automatic start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Section C403.2.4, IECC 2012. |
11/05/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a water pressure regulator conforming to ASSE 1003 or CSA B356 to limit the water pressure to 80 PSI or less. Reference: Section 604.8, IPC 2012. 2. Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson. |
11/05/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/08/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/20/2013 | LAITH ALSHAMI | ENGINEERING | REVIEW | Denied | Laith Alshami, Engineering and Floodplain Review, 11/20/2013, Development Package has nott been approved yet. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/21/2013 | CPIERCE1 | REJECT SHELF | Completed |