Review Details: CELL TOWER/ANTENNAS
Permit Number - T13CM06371
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/22/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 10/22/2013 | GREGORY MCNEAL | COMMUNICATIONS | REVIEW | Approved | |
| 10/22/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM06371 New Cell Tower Site 1. Provide a panel schedule showing all circuits connected, loads and breaker sizes. 2. The Panel has a 22Kaic value, if value over 10Kaic will this be a fully rated system ? Ray T Majuta Elect Plan Review PDSD, Tucson 10/22/2013 Ray.Majuta@tucsonaz.gov |
| 10/25/2013 | JASON GREEN | ENGINEERING | REVIEW | Reqs Change | DATE: October 25, 2013 SUBJECT: 1740 E Fort Lowell Rd- Cell Tower & CMU Wall Installation TO: Brendon Thomson LOCATION: T13S R14E Sec31, Ward 3 REVIEWERS: Jason Green, CFM ACTIVITY: T13CM06371 (Building Plan) and T13OT01230 (Floodplain Use Permit) SUMMARY: Engineering Division of Planning & Development Services Department has received and reviewed the Building Plan (T13CM06371) and Floodplain Use Permit (T13OT01230) for the above referenced property and does not recommend approval of the at this time. The subject property is entirely located within a Special Flood Hazard Area (SFHA), Zone AE as shown on the Flood Insurance Rate Map (FIRM), Community- Panel No. 040073-04019C-1689L, effective date June 16, 2011. Per Section 26-5.2 of the Tucson Code no development, storage of materials or equipment or other uses shall be permitted which acting alone or in combination with existing uses, create a danger or hazard to life or property. In order to process your application for development within the floodway fringe of the Wilson Avenue Wash the following information is required: BUILDING PLAN: 1) TC Sec.26-5.2.5: Revise the building plan and CMU wall detail to label and dimension the required wall openings to prevent encroachment within the floodplain. Or provide a drainage statement that shows the enclosure will not increase the base flood elevation more than one-tenth of a foot. The openings shall provide a total net area of not less than one square inch for every square foot of area enclosed, excluding any bars, louvers, or other covers of the opening. The bottom of the openings must be no higher than one foot above the higher of the exterior or interior grade or floor immediately below the opening and must be located with a minimum of 1 opening on each wall, but preferably with 2 opening on each wall. 2) TC Sec.26-5.2.10: Provide a note on the Building Plan to clearly state that all structures, material or equipment will be anchored to prevent flotation. Specifically for equipment such as generators that utilize gas or oil components. 3) TC Sec.26-5.2.11: Revise the building plan and platform details to show that the top of the bar grate and/or the lowest point of all service facilities such as the electrical components or generator equipment, whichever is lower, is at or above the regulatory flood elevation (2382.7 feet NAVD 1988). Provide the elevation in place of the referenced "2'-0 Top of Bar Grate dimension." 4) TC Sec.26-11.2.h: An Elevation Certificate (FEMA Form 086-0-33) must be prepared by a state registered land surveyor and submitted to our office prior to Final Electrical and Building Final inspections. The ELCERT will be issued with the Building Permit with all applicable Community Information filled out. GENERAL COMMENTS: Please provide a revised Building Plan with revised details that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments. For any questions or to schedule meetings call me at 837-4929. Jason Green, CFM Senior Engineer Associate Engineering Division Planning & Development Services |
| 10/28/2013 | PETER MCLAUGHLIN | PLANNING-CITY HALL | REVIEW | Approved | |
| 10/28/2013 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 11/12/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Need seal and signature on structural drawings of structural engineer that completed the calculations. 2. Please provide certification of special inspectors. The two part form is located on our website. 3. Please provide structural calculations for monopole foundations including option design. END OF REVIEW |