Permit Number: T13CM06370
Parcel: 125073460

Address:
422 N PLUMER AV

Review Status: Active

Review Details: PLANS OK TO SUBMIT - RES

Permit Number - T13CM06370
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
10/17/2013 MICHAEL ST. PAUL ZONING REVIEW Denied P&DS TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T13CM06370
422 North Plumer Avenue
New single family residence (SFR)


TRANSMITTAL: October 17, 2013


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).


This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). The parapet wall height is twenty-five (25) feet. The required setback to both the north and south property lines is sixteen (16) feet, eight (8) inches. The proposed setback to the north property line is six (6) feet, and the proposed setback to the south property line is eleven (11) feet, six (6) inches.
10/17/2013 ANY NPPO REVIEW Active
10/17/2013 ANY ENGINEERING REVIEW Active
10/17/2013 ANY BUILDING-RESIDENTIAL REVIEW Active