Review Details: RESUBMITTAL
Permit Number - T13CM06297
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/05/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM06297 5300 E Los Reales Tire Wash 1. The Tire Wash Electrical Plans were not resubmitted with this group. I understand (from Metro) that plans are being revised and to be submitted at a later time. Ray T Majuta Elect Plan Review PDSD, Tucson 11/5/2013 Ray.Majuta@tucsonaz.gov 520-837-4988 |
| 11/06/2013 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 11/14/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/18/2013 | LEERAY HANLY | PLUMBING-COMMERCIAL | REVIEW | Approved | The civil plans are not a subsitute for plumbing plans. The only reference is for a 3/4" water line over to be installed to tire-wash. Please provide complete product specifications to justify 3/4" water supply. Include all backflow data |
| 11/18/2013 | LHANLY1 | WATER | REVIEW | Approved | insufficient information provided for review |