Permit Number: T13CM06289
Parcel: 14039052E

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T13CM06289
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/17/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied See comments for T13CM06288
10/18/2013 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved
10/22/2013 KEN BROUILLETTE FIRE REVIEW Approved
10/22/2013 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: David Rivera
Principal Planner

PROJECT: T13CM06289
5300 e Los Reales Road
New Scale House Building

TRANSMITTAL DATE: October 22, 2013

DUE DATE: October 29, 2013

COMMENTS:

01. Zoning has reviewed the building plans for compliance and consistency with the development package site plan. While the building plans are in substantial compliance with the unapproved version of the DP zoning cannot approve the building plans until the Revised version of the DP is approved and stamped.

02. Once the DP site has been approved and all building trades reviewers have approved the building plan, zoning will approve and sign off on the permit application for the New Scale House Building.

03. Any changes that are made to the DP site plan that affect the proposed building must be addressed on both the building plans package and site plan.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.
10/23/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide the gutter and downspout design for the canopy. Reference: Sections 1106.1 and 1106.6, IPC 2012.
10/23/2013 ROBERT SHERRY WATER REVIEW Approved
10/24/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Complete the Envelope Compliance Certificates by checking the appropriate line items in Section 3, the Air Leakage, Component Certification, and Vapor Retarder Requirements. Supporting documentation shall be either on the drawings or in the project manual.
2. Show the R-value for the furring of the exterior walls used in the Envelope Compliance Certificate on the drawings.
3. Provide the calculations and other supporting documentation to justify the U-factor used for the roofs in the Envelope Compliance Certificate. Note that the roofs are exempt from the requirement for having a high albedo coating because the roofs are constantly shaded.
10/24/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied Reference T12CM06288 Building Comments

Final Status

Task End Date Reviewer's Name Type of Review Description
11/04/2013 CPIERCE1 REJECT SHELF Completed