Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM06259
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2013 MARTIN BROWN FIRE REVIEW Denied ADD 2012 IFC AND CHANGE IBC TO 2012 AND RESUBMIT-KEN B
11/06/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET G-001; PROJECT DATA (GOVERNING CODES): THE CURRENT BUILDING CODE FOR THE CITY OF TUCSON IS THE 2012 IBC. REVISE THE NOTE AND VERIFY ALL REQUIREMENTS OF THE 2012 EDITION AND THE CITY OF TUCSON AMENDMENTS ARE SATISFIED.
2. SHEET G-001; PROJECT DATA (GOVERNING CODES): REMOVE THE REFERENCE TO THE 1992 ADAAG, AND REVISE THE ICC/ANSI REFERENCE TO THE 2009 EDITION.
3. SHEET G-001: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE SHEET INDEX, PROJECT GENERAL NOTES, CODE GENERAL NOTES, INDEX, AND PROJECT DATA.
4. SHEET G-001; FLOOR PLAN: ARE THE NUMBERS SHOWN IN MOST ROOMS INDICATING THE OCCUPANCY LOAD FOR THAT ROOM? IF SO, THEY DO NOT CONFIRM THE OCCUPANT LOAD OF 40 AS LISTED IN THE PROJECT DATA. COORDINATE THE OCCUPANT LOAD.
5. SHEET G-001; WALL TYPE DETAILS: PROVIDE EXPLANATIONS FOR THE WALL TYPES INDICATED BY F/06, F/07, S/24, AND S/04. THE WALL TYPE LEGEND INDICATES "C" AS A FULL HEIGHT WALL AND "E" AS A WALL TO 6" ABOVE THE CEILING. FOR WALLS THAT END JUST ABOVE THE CEILING, PROVIDE A DETAIL FOR HOW THE WALL IS BRACED, INCLUDING BRACING SIZE AND SPACING, AND THE CONNECTION OF THE BRACING TO THE STRUCTURE ABOVE AND TO THE TOP OF THE WALL.
6. SHEET G-001; FLOOR PLAN: REMOVE THE ROOM NUMBERS FROM THIS PLAN.
7. SHEET G-001; FLOOR PLAN: PROVIDE A NORTH ARROW ON THE PLAN.
8. SHEET A-101; ACCESSIBLE DETAILS: PROVIDE DIMENSIONED ELEVATIONS OF THE GRAB BARS AND THE CONTROL/HANDSHOWER LOCATIONS IN THE SHOWER PER THE ICC/ANSI A117.1, SECTION 608.
9. SHEET A-101: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE PLAN GENERAL NOTES, THE FLOOR PLAN ROOM IDENTIFICATION NAMES, KEYNOTES, ACCESSIBLE DETAILS NOTES, AND ALL PLAN DIMENSIONS.
10. SHEET A-101; ACCESSIBLE DETAILS: A NOTE UNDER THE TITLE REFERENCES THE 2003 ICC/ANSI. REVISE TO THE 2009 EDITION, AND VERIFY ALL ACCESSIBILITY REQUIREMENTS FOR THAT EDITION ARE MET.
11. SHEET A-102: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE SITE PLAN NOTES, KEYNOTES, REFLECTED CEILING GENERAL NOTES, FLOOR PLAN ROOM IDENTIFICATION NAMES, ALL PLAN DIMENSIONS, AND EQUIPMENT PLAN NOTES.
12. SHEET A-102; BOOM SUPPORT DETAIL 5A: INDICATE ON A PLAN AND IDENTIFY WHERE THIS DETAIL IS APPLICABLE.
13. SHEET A-102; REFLECTED CEILING PLAN KEYNOTES: IS THERE A DESCRIPTION OF THE CEILING SYSTEMS 1 AND 2 ON THE DRAWINGS? VERIFY.
14. SHEET A-104: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE CASEWORK GENERAL NOTES, CASEWORK NOMENCLATURE, AND DETAIL 1 AND 2 KEYNOTE REFERENCES.
15. SHEET A-104; BREAK ROOM ELEVATION: INDICATE ON A DETAIL THE HEIGHT OF THE CABINET/SINK (MAXIMUM 2'-10" ABOVE THE FLOOR).
16. GENERAL: INCLUDE A COPY OF THE APPROVED SITE PLAN WITH EACH SET OF DRAWINGS.
17. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/12/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM06259
3935 E Fort Lowell #02
TI Surgery Center

1. Sheet E101, describe the ER dots at exits to outdoors.
2. Sheet E201, identify circuits that do not have a panel designation.
3. Sheet E301, identify circuits that do not have a panel
designation.
4. Sheet E301, circuit ESEQ-11,13,15 shown going to RTU-1B not showing same use in panel schedule.
5. Sheet E501, fault current summary, indicate on this sheet that circuit breakers in panels to be fully rated(same as panels) or provide information on Series Rated Systems if to be used.
6. Sheet E501, provide information showing compliance with 2011 NEC, 517.26 and 700.27 conserning Selective Coordination System.
7. Sheet E501, Panel LPC1 shows 277 voltages on circuit 30, this panel is fed from Panel LPA1 which is 120/208 volt ?
Describe the Wattstopper Panel and how two circuit 30's are shown. The va's for circuit LPA1-30 are different than the ones shown in the LPC1 Panel ?
8. There are no outside lighting fixtures for the site or on the building ? Site Lighting may be existing please indicate, what about outdoor building lighting ? If to be includesd must comply with City of Tucson Outdoor Lighting Code 2012.
9. Chect all boxes that apply on Sheet E903, IECC Compliance Certificate under #4, Requirement Checklist.
10. Concerning Med Gas. please clearify if type used is considered hazardous or non hazardous per 517.60- 2011 NEC. If hazardous apply wiring methods (note on plan) per 517.61

Ray T Majuta
Electrical Plan Review
PDSD, Tucson
11/14/2013
Ray.Majuta@tucsonaz.gov
520-837-4988
11/14/2013 ROBERT SHERRY WATER REVIEW Denied Show that the size of the proposed water meter complies with the size requirements of Tucson Water for the calculated water demand. Note: use the fixture units for the total water use for each fixture (e.g. use 3.0 water fixture units for a service sink instead of 2.25 water fixture units which is only for cold water or hot water for the sink).
11/14/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 107.2.1, IBC 2012.
2. Provide a site drawing showing the size, route, and slope of the building sewer and the location of its connection to the public sewer. Reference: Section 107.2.1, IBC 2012.
3. Provide water supply isometrics and waste and vent isometrics. Reference: Section 107.2.1, IBC 2012.
4. The term "private" for plumbing fixtures applies to fixtures that are located in a residence or apartment, non-public toilet rooms in hotels or motels, and are intended for the use of a family or an individual. None of the plumbing fixtures shown on the plumbing plan appear to fit the definition of private; revise the water demand calculation on sheet P 901. Reference: Section 202, IPC 2012.
5. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Sections 416.5 and 607.1, IPC 2012 and Section C404.3, IECC 2012.
6. Provide a shower control valve that complies with the requirements of Section 424.3, IPC 2012.
7. Clarify the purpose for the installation of a well tank and pump rated for 30 GPM considering the demand for the building water supply is approximately 60 GPM. Reference: Section 602.1, IPC 2012.
8. Clarify the installation of ST-1 as shown in detail 6/P801 with the piping plan on sheet P401. Reference: Section 107.2.1, IBC 2012.
9. Provide calculations showing how the water supply piping has been sized. Reference: Sections 604.1 and 604.3, IPC 2012.
10. Verify that the pipe sizes called out for the flush valves will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper or CPVC piping). At a minimum design flow rate of 25 GPM for a siphonic, flush-valve water closet, a 1" Type L copper pipe has a flow velocity of 9.7 FPS. Reference: Table 604.3, IPC 2012.
11. Provide a full-open valve for the water service at the building entrance. Reference: Section 606.1(2), IPC 2012.
12. Show how accommodation for the thermal expansion of the hot water system is being provided. Reference: section 607.3, IPC 2012.
13. Appliances (e.g. ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.
11/14/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The building shell being modified in this activity does not appear to have been conditioned. Section C101.4.5, IECC 2012 requires the space to be brought into full compliance with the current energy code. Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.
2. Revise the HVAC load calculations, using the exterior design conditions specified by Section C302.1, IECC 2012, as amended by the City of Tucson.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/23/2013 CPIERCE1 REJECT SHELF Completed