Permit Number: T13CM06137
Parcel: 126191550

Address:
621 S ERIN AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T13CM06137
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2013 RAFAEL CANCINO BUILDING-RESIDENTIAL REVIEW Reqs Change T13CM06137

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide revised plans and calculations, highlighting any changes or with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2012 IRC with amendments on 1/1/2012. Show the current code reference on the plans.

GENERAL NOTES:

" Limit all code references to those recognized by the City of Tucson. Adopted 2012 codes are listed at the Planning & Development Services web site. Show the code references used for the design.
" Correct spelling errors throughout plan sheets.

FOUNDATION PLANS:

1. Section A is located at sheet A3, please correct.

FLOOR PLANS:

1. Specify window sizes.
2. Section A is on sheet A3, please correct.

STRUCTURAL PLANS:

1. Show that trusses are to be manufactured by state approved truss manufacturer.

ELEVATIONS:

1. Floor plan calls for 3/8" sheathing. Elevations and details call for 5/8" sheathing. Please clarify.

SECTIONS - DETAILS:

1. Show wood framing members resting on concrete as pressure treated, R319.1 item 2 Provide treated sill plates bearing on concrete slabs, R317.1 item 3.
2. Show ceiling gypsum board as ½" sag resistant or 5/8" thick gypsum board.
3. Show minimum 7" concrete embedment of anchor bolts.

PLUMBING PLANS:

1. Provide a water hammer arrester for quick-closing valves serving the clothes washer, P2903.5.


If you have any questions please contact:
Rafael Cancino
(520) 909-4891
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/06/2013 CPIERCE1 REJECT SHELF Completed