Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM06126
Parcel: 125073980

Address:
2526 E 6TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM06126
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2013 DAVID RIVERA ZONING REVIEW Approved
11/22/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide listing information for the new convection oven and the manufacterer's installation instructions.
11/22/2013 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
11/22/2013 ROBERT SHERRY WATER REVIEW Approved
11/22/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/22/2013 JASON GREEN ENGINEERING REVIEW Approved
11/22/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the specifications for the water heater.
2. Horizontal vents below grade are not allowed indoors.
3. All vents shall rise to at least 6" above the flood rim of the highest fixture served prior to joining other vents.
11/22/2013 MARTIN BROWN FIRE REVIEW Approved
11/22/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/25/2013 SPOWELL1 WWM REVIEW Needs Review