Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM06116
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/07/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
10/07/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/07/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
10/07/2013 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
10/08/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the ventilation calculations per Section 403.3, IMC 2012. Verify that the airconditioning unit can handle the OSA load. Provide a total exhaust of 0.6 CFM per SF for the nail salon area. |
10/08/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
10/08/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/08/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Clarify the location of the backflow preventers for the spa chairs. |
10/08/2013 | ERICA SANCHEZ | WWM | REVIEW | Passed | |
10/08/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved |