Permit Number - T13CM06073
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/18/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/18/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/18/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/18/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/18/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM06073 5830 E Pima 1. The fault current calculation should start at 75,000 aic per TEP (Utility) SR Book. Where is the 50,000 aic value obtained. 2. The fault current sheets are required to have an address, be stamped by the EE of record, and dated. Ray Majuta Elect Plan Review 10/18/2013 |
| 10/18/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |