Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T13CM06046
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/17/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/31/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
01/31/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The wall descriptions used for COMcheck do not correspond to the wall descriptions shown on a3.1, Wall Types. [Third comment: The building components shown on the Envelope Compliance Certificate are not clearly shown on the drawings. Include the roll-up door and the pass-through window at the bar as components in the Envelope Compliance Certificate.] [Second comment: Provide a copy of the COMcheck Envelope Compliance Certificate for the addition to the building. Verify that the building components shown on the Envelope Compliance Certificate are clearly shown on the drawings.] [Initial comment: Revise the energy code compliance for the addition to the building envelope using calculations based on the current code. Reference: Sections C101.4.3, C101.5, C103.2, C303, and C401.2.1, International Energy Conservation Code 2012.] |
02/10/2017 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/22/2017 | MMENDIB1 | OUT TO CUSTOMER | Completed |