Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T13CM06046
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/28/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide plans sealed by an Arizona Registrant, not marked as "Preliminary". Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Provide a current site utility plan as referenced on sheet p1.1. Reference: Section 107.2.1, IMC 2012. 3. Complete the gas table on sheet p9.1; coordinate the gas inputs for AC-2 and AC-3 with the equipment schedule on sheet m9.1. Reference: Section 107.2.1, IMC 2012. 4. Provide a direct connection to the building drainage system for all plumbing fixtures except as allowed by Chapter 8, IPC 2012 (e.g. all 5 hand sinks and the soiled dish table). Reference: Section 301.3, IPC 2012. 5. Provide third-party listing and material standards for all plumbing fixtures being provided by others. Reference: Sections 303.4 and 402, IPC 2012. 6. Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03. 7. All appliances that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC 2012 with a direct-connection to water shall be protected against backflow. Specify the device to be used for each appliance connection and show it on the riser diagram. (Water supply connections to beverage dispensers shall be protected with backflow preventers conforming to ASSE 1022.) Reference: Sections 608.15 and 608.16, IPC 2012. 8. Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012. 9. Verify that all horizontal vents forming branch vents, relief vents, or loop vents are located at least 6" above the flood rim of the highest fixture served. Reference: Section 905.5, IPC 2012 10. Provide roof drainage calculations based on the 100-year hourly rainfall rate for Tucson, 3" per hour. Reference: Sections 1106.1, 1106.4, and 1108.3, IPC 2012 |
| 09/29/2016 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/29/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/30/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide plans sealed by an Arizona Registrant, not marked as "Preliminary". Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Coordinate the AC units shown on the roof plan with the AC units scheduled on sheet m9.1. Reference: section 107.2.1, IBC 2012. 3. Revise the energy code compliance for the addition to the building envelope using calculations based on the current code. Reference: Sections C101.4.3, C101.5, C103.2, C303, and C401.2.1, International Energy Conservation Code 2012. 4. Provide heating and cooling load calculations that justify the capacities of the additional heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012. |
| 10/05/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/13/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide full compliance with Tucson/Pima County Outdoor Lighting Code. |
| 10/18/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | T13CM06046 ARCHITECTURAL COMMENTS: 1. SHEET a0.1; PROJECT DATA (AREA + OCCUPANCY): PLEASE INDICATE ON THE DRAWINGS THE SPECIFIC CODE SECTION THAT ALLOWS UNLIMITED AREA FOR AN A-2 USE, TYPE VB CONSTRUCTION. 2. SHEET a0.1; PROJECT DATA (PLUMBING FIXTURES): PLEASE INDICATE ON THIS SHEET THE REQUIRED SERVICE SINK PER THE IBC TABLE 2902.1. 3. SHEET a2.0; DEMOLITION PLAN: A NOTE ON THE PLAN INDICATES 'EXTENT OF PREVIOUSLY PERMITTED AREA OF NEW CONSTRUCTION T13CM06046 FOR REFERENCE ONLY'. ARE THERE NEW CHANGES TO THIS AREA FOR THE CURRENT PERMIT? PLEASE CLARIFY AND OMIT THE NOTE AS REQUIRED. 4. SHEET a3.0; FLOOR PLAN: PER THE IBC SECTION 1109.11, AT LEAST 5% OF SEATING AND STANDING SPACES SHALL BE ACCESSIBLE. PLEASE INDICATE ON THIS SHEET THE CALCULATION FOR THE REQUIRED NUMBER OF ACCESSIBLE SPACES, AND INDICATE THOSE SPACES ON THE PLAN. 5. SHEET a3.0; GENERAL FLOOR PLAN NOTES: PLEASE REVISE NOTE 18 TO 'SEE SHEET a8.1 FOR BATHROOM ELEVATIONS. 6. SHEET a3.0; GENERAL FLOOR PLAN NOTES: NOTE 21 SHOULD REFERENCE SHEET FS 3.0 FOR FLOOR DRAINS. PLEASE REVISE. 7. SHEET a3.0; FLOOR PLAN KEY NOTES (NOTE 6): IS THE REFERENCE TO SHEET a3.0 CORRECT? PLEASE VERIFY. 8. SHEET a3.0; FLOOR PLAN KEY NOTES (NOTE 36): IS THE REFERENCE TO DETAIL 11/a9.0 CORRECT? PLEASE VERIFY. 9. SHEET a3.0; FLOOR PLAN KEY NOTES (NOTE 70): IS THE REFERENCE TO SHEET a3.1 CORRECT? PLEASE VERIFY. 10. SHEET a3.0 (FLOOR PLAN); SHEET a5.1 (DOOR SCHEDULE): FLOOR PLAN KEY NOTE 17 INDICATES PANIC HARDWARE AT DOOR 102b, WHILE THE DOOR SCHEDULE DOES NOT INDICATE PANIC HARDWARE. PLEASE CLARIFY. 11. SHEET a3.1; PLAN: THE WALL TYPE F (INDICATED ALONG THE EAST SIDE OF THE BAR ALL THE WAY UP TO THE NORTH EXTERIOR WALL, AND ALONG THE SOUTH SIDE OF THE BAR) IS DESCRIBED AS A ONE HOUR RATED WALL (U.L. #415). PLEASE VERIFY THIS WALL IS REQUIRED TO BE A RATED ASSEMBLY. ARE ALL OF THE DOORS AND STOREFRONTS IN THIS WALL ALSO RATED? THE DOOR SCHEDULE (SHEET a5.1) DOES NOT INDICATE DOORS 102a, 102b, 103a, 102c, 102e, OR 102d AS RATED. PLEASE CLARIFY. 12. SHEET a3.2; ROOF PLAN: PLEASE FINISH THE SECTION CUT AT THE SOUTH PERFORATED METAL SCREEN WALL (NOTE 16). 13. SHEET a6.0; TITLE BLOCK: THE TITLE BLOCK INDICATES 'INTERIOR ELEVATIONS'. PLEASE REVISE. 14. SHEETS a6.0, a6.1, a7.0, a8.0, AND a8.1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE. 15. SHEET a7.0; SECTION 2: THE GRID LINES a AND b DO NOT MATCH SECTION 1/a7.0. PLEASE REVISE. 16. SHEET a7.0 (SECTIONS 1 AND 2); SHEET a9.2 (DETAIL 48): SHEET a9.2 INDICATES THE DETAIL IS 'NOT USED', WHILE THE DETAIL IS REFERENCED ON SECTIONS 1/a7.0 AND 2/a7.0. PLEASE CLARIFY. 17. SHEET a7.0; SECTION 3: A DETAIL REFERENCED NEAR GRID a IS NOT COMPLETE. PLEASE REVISE. 18. SHEET a9.2 (EXISTING WALL TYPE "C"-DETAIL 49); SHEET a3.1 (WALL TYPES): WALL TYPE C ON SHEET a3.1 IS AN EXISTING ADOBE WALL, WHILE DETAIL 49 INDICATES A METAL STUD WALL. PLEASE CLARIFY. 19. GENERAL: PLEASE PROVIDE CONSISTENT GRID LINES ON ALL PLANS. 20. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. STRUCTURAL COMMENTS: 21. SHEET S2.0 (FOUNDATION PLAN); STRUCTURAL CALCULATIONS: ARE THERE CALCULATIONS FOR THE MASONRY WALL MW2 INCLUDED IN THIS SUBMITTAL? PLEASE PROVIDE. 22. SHEET S2.0 (FOUNDATION PLAN); STRUCTURAL CALCULATIONS: ARE THERE CALCULATIONS FOR THE MASONRY WALL FOOTINGS MW1 AND MW2 INCLUDED IN THIS SUBMITTAL? PLEASE PROVIDE. 23. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 10/21/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 10/25/2016 | ERICA SANCHEZ | WWM | REVIEW | Reqs Change | Project for 201 N. 4th Ave (T13CM06046) needs the following: 1.) Type 3 Capacity- Please submit online to (RWRDCapacityResponse@pima.gov) 2.) IWC- Steven Valencia (Steven.Valencia@pima.gov) 3.) Fees for 1 ½" water meter $27,030.00 4.) Call out H.C.S tap and size |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/30/2016 | AHINES2 | OUT TO CUSTOMER | Completed |