Review Details: RESUBMITTAL
Permit Number - T13CM06046
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/25/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/29/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | A light-duty appliance that does not produce grease or smoke but does produce products of combustion, shall be located under a Type II hood per Section 507.2.2, IMC 2012. [Initial comment: Show the manufacturer's minimum mounting height for the infra-red heaters and verify the mounting angle for the heaters does not result in insufficient clearances. Reference: Section 303.1, IFGC 2012.] |