Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM06037
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/04/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the new plumbing fixtures are to be connected to the existing water supply and sanitary waste systems (e.g. provide waste, vent, and water supply riser diagrams). Reference: Section 107.2.1, IBC 2012. 2. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. 3. Provide a complete diagram of the natural gas distribution system showing the all of the loads, developed lengths, and the layout of the distribution piping. Reference: Section 107.2.1, IBC 2012 and Section 402.3, IFGC 2012. |
11/05/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/05/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide structural calculations and details to show that the new Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012. 2. Show that the enclosure for the new Type I hood complies with Section 507.9, IMC 2012 with regard to a smooth, cleanable, non-absorbent, and non-combustible material installed between the hood and the wall. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/19/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |
12/19/2013 | CPIERCE1 | REJECT SHELF | Completed |