Permit Number: T13CM06037
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM06037
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the new plumbing fixtures are to be connected to the existing water supply and sanitary waste systems (e.g. provide waste, vent, and water supply riser diagrams). Reference: Section 107.2.1, IBC 2012.
2. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
3. Provide a complete diagram of the natural gas distribution system showing the all of the loads, developed lengths, and the layout of the distribution piping. Reference: Section 107.2.1, IBC 2012 and Section 402.3, IFGC 2012.
11/05/2013 ROBERT SHERRY WATER REVIEW Approved
11/05/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide structural calculations and details to show that the new Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012.
2. Show that the enclosure for the new Type I hood complies with Section 507.9, IMC 2012 with regard to a smooth, cleanable, non-absorbent, and non-combustible material installed between the hood and the wall.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/19/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
12/19/2013 CPIERCE1 REJECT SHELF Completed